All op amps were
powered from dual or split supplies, and this is not the case in
today’s world of portable, battery-powered equipment. When op amps
are powered from dual supplies (see Figure 4–1), the supplies are
normally equal in magnitude, opposing in polarity, and the center tap
of the supplies is connected to ground. Any input sources connected
to ground are automatically referenced to the center of the supply
voltage, so the output voltage is automatically referenced to ground.
Figure 4–1.
Split-Supply Op Amp Circuit
Single-supply
systems do not have the convenient ground reference that dual-supply
systems have, thus biasing must be employed to ensure that the output
voltage swings between the correct voltages. Input sources connected
to ground are actually connected to a supply rail in single-supply
systems. This is analogous to connecting a dual-supply input to the
minus power rail. This requirement for biasing the op amp inputs to
achieve the desired output voltage swing complicates single-supply
designs.
When the signal
source is not referenced to ground (see Figure 4–2), the voltage
difference between ground and the reference voltage is amplified
along with the signal. Unless the reference voltage was inserted as a
bias voltage, and such is not the case when the input signal is
connected to ground, the reference voltage must be stripped from the
signal so that the op amp can provide maximum dynamic range.
Figure 4–2.
Split-Supply Op Amp Circuit With Reference Voltage Input
An input bias
voltage is used to eliminate the reference voltage when it must not
appear in the output voltage (see Figure 4–3). The voltage, VREF,
is in both input circuits, hence it is named a common-mode voltage.
Voltage feedback op amps reject common-mode voltages because their
input circuit is constructed with a differential amplifier (chosen
because it has natural common-mode voltage rejection capabilities).
Figure 4–3.
Split-Supply Op Amp Circuit With Common-Mode Voltage
When signal sources
are referenced to ground, single-supply op amp circuits exhibit a
large input common-mode voltage. Figure 4–4 shows a single-supply
op amp circuit that has its input voltage referenced to ground. The
input voltage is not referenced to the midpoint of the supplies like
it would be in a split-supply application, rather it is referenced to
the lower power supply rail. This circuit does not operate when the
input voltage is positive because the output voltage would have to go
to a negative voltage, hard to do with a positive supply. It operates
marginally with small negative input voltages because most op amps do
not function well when the inputs are connected to the supply rails.
Figure 4–4.
Single-Supply Op Amp Circuit
The constant
requirement to account for inputs connected to ground or different
reference voltages makes it difficult to design single-supply op amp
circuits. Unless otherwise specified, all op amp circuits discussed
in this chapter are single-supply circuits. The singlesupply may be
wired with the negative or positive lead connected to ground, but as
long as the supply polarity is correct, the wiring does not affect
circuit operation.
Use of a
single-supply limits the polarity of the output voltage. When the
supply voltage VCC = 10 V, the output voltage is limited to the range
0 ≤ Vout ≤ 10. This limitation precludes negative output voltages
when the circuit has a positive supply voltage, but it does not
preclude negative input voltages when the circuit has a positive
supply voltage. As long as the voltage on the op amp input leads does
not become negative, the circuit can handle negative input voltages.
Beware of working
with negative (positive) input voltages when the op amp is powered
from a positive (negative) supply because op amp inputs are highly
susceptible to reverse voltage breakdown. Also, insure that all
possible start-up conditions do not reverse bias the op amp inputs
when the input and supply voltage are opposite polarity.
No comments:
Post a Comment